MPE
MPE Limited
Hammond Road
Knowsley Industrial Park Liverpool
L33 7UL
Contact
T: +44 (0)151 632 9100
E: sales@mpe.co.uk

Standard Performance EMC Filter Range

Standard Performance EMI filters for electrical connection to SP&N and TP&N mains distribution systems. The filters offer attenuation against electromagnetic noise present on the power lines between the ranges of 100kHz to 18GHz to 100dB. The supply should have a balanced return current and the case needs a solid low impedance connection to earth potential.

Insertion Loss Performance

Asymmetric attenuation shown as measured in 50Ω system, at all loading conditions, in accordance with CISPR-17.
Performance curve meets 100dB attenuation from 100kHz to 18GHz.

Standard-Performance-EMC-Filter-Range

Rated CurrentPart NumberDC Resistance
(mΩ)
Earth Leakage*
(A)
Length
(mm)
Width
(mm)
Height
(mm)
Approximate Weight
(kg)
16ADS23752251.80310175908
32ADS23332101.805502059516
63ADS2333461.855020510520
100ADS2333641.8064020512022
200ADS2370822.6066047513560
400ADS260500.34.401250475150110
Rated CurrentPart NumberDC Resistance
(mΩ)
Earth Leakage*
(A)
Length
(mm)
Width
(mm)
Height
(mm)
Approximate Weight
(kg)
32ADS23333102.205504109522
63ADS2333562.755041011032
100ADS2333743.1566041013545
200ADS2370926.366057515070
250ADS309290.56.31020575200100
400ADS260510.36.301250575150120
800ADS50026A0.23.151800864285250
800ADS50026C0.23.151700864285250
1200ADS50027A0.13.6522001000300300
1200ADS50027C0.13.6519001000300300
1200ADS50027A0.13.6522001000300300
1200ADS50027C0.13.6519001000300300

Rated Voltage

  • 250VAC (SP&N) 50/60Hz
  • 440/250VAC (TP&N) 50/60Hz

Alternative Voltage

  • Also suitable for 208/120VAC and 480/277VAC
  • Alternative surge arrestors may be required.
  • TP&N filters are also suitable for three phase supplies without neutral. In such installations, the neutral terminal should be left unconnected.

Rated Current

  • 6A to 1200A (each individual line, see table)

Current Overload

  • 10 x maximum rated current for 1 sec.
  • 1.5 x max rated current for 10 minutes.

Discharge time

  • 30 seconds to below 30V (filter incorporates discharge resistors)
  • If sockets or plugs are used for connection, ensure that no pins or un-insulated parts are accessible by none qualified personnel upon removal.

Temperature Rise

  • 25°C case rise on full load

Temperature Range

  • -45°C to +85°C Storage
  • -45°C to +50°C Working

MTBF

  • >0.8 million hours (calculated using Mil Hdbk 217D)

Surge Suppression (optional)

  • 275VAC at 215J 10kA 8/20μs
  • All filters can be supplied with an integral metal-oxide varistor, fitted between each input terminal and earth. Add a suffix “V” to end of part code.
  • Screened Rooms, Server Supplies & EMC Test Chambers
  • Meets TEMPEST requirement for power filters to NATO SDIP 29/1
  • Supports compliance to MIL STD 461 & DEF STAN 59 411
  • All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:
    • Mil-F-15733
    • Mil-Std-220C
    • CISPR17:2011/BS EN 55017:2011
    • UL1283
    • LVD 2014/35/EU
    • NATO STANAG 1008 Ed.9 shipboard supplies
    • DEF-STAN 59-411/MIL-STD-461
    • RoHS (2011/65/EU) & LVD (2014/35/EU)
    • UKCA & CE
    MPE Part CodeDescriptionNSN
    DS2375216A Single Phase5915-99-968-7487
    DS2333232A Single Phase5915-99-176-8426
    DS2333463A Single Phase5915-99-152-3079
    DS23336100A Single Phase5915-99-391-4527
    DS23708200A Single Phase5915-99-156-5318
    DS26050400A Single Phase5915-99-847-7146
    DS236196A Three Phase5915-99-291-1718
    DS2333110A Three Phase5915-99-377-6256
    DS2333332A Three Phase5820-99-570-1166
    DS2333563A Three Phase5915-99-371-3551
    DS23337100A Three Phase5915-99-671-1575
    DS23709200A Three Phase5915-99-959-4382
    DS30929250A Three Phase5915-99-918-6144
    DS26051400A Three Phase5915-99-845-4990
    DS XXXXX / X / X
    • Filter Part Number
    • Suffix C for standard cable entry
    • For other cable entries, see Installation Details page
    • Add suffix V for transient suppressed filter
    e.g. DS23330CV

    ORDERING CODE

    DS XXXXX / X / X

    • Filter Part Number
    • Suffix C for standard cable entry
    • For other cable entries, see Installation Details page
    • Add suffix V for transient suppressed filter

    e.g. DS23330CV