MPE
MPE Limited
Hammond Road
Knowsley Industrial Park Liverpool
L33 7UL
Contact
T: +44 (0)151 632 9100
E: sales@mpe.co.uk

Multi-Line AC Control Line Filters

A range of multi-line filters suitable for filtering ac control lines and low current power lines on shielded rooms and general installations. All versions are available with transient suppression if required.

All MPE control line filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:

Mil-F-15733
Mil-Std-220C
CISPR17:2011/BS EN 55017:2011
UL1283
LVD 2014/35/EU

GENERAL SPECIFICATION

Rated Voltage
250V a.c. 50/60Hz or 600V d.c.
Test Voltage
2250V dc (prior to fitting any transient suppressors)
Rated Current
1A to 10A
Insulation Resistance
> 100MΩ (before fitting discharge resistors)
Discharge Resistors
560kΩ each line to case
Discharge time to below 34V
< 10s
Maximum Temperature Rise on Full Load
25ºC
Full Load Operating Temperature Range
-40ºC to +50ºC

RANGE AVAILABLE

Current Rating (A) MPE Part Number Number Of Lines Volt Drop (mV) Heat  Dissipation (W) Major Dimensions (mm) Approx Weight (kg)
A B C
1 DS23778 2 2.7 2.7 350 90 45 2.5
2 DS25791 2 1.3 2.6 350 90 45 2.5
5 DS25260 2 1 5 350 90 45 2.5
10 DS25794 2 0.7 7 350 90 45 2.5
1 DS25263 4 2.7 2.7 350 180 45 5
2 DS25792 4 1.3 2.6 350 180 45 5
5 DS25261 4 1 5 350 180 45 5
10 DS25795 4 0.7 7 350 180 45 5
1 DS25264 8 2.7 2.7 350 360 45 10
2 DS25793 8 1.3 2.6 350 360 45 10
5 DS25262 8 1 5 350 360 45 10
10 DS25796 8 0.7 7 350 360 45 10

TRANSIENT SUPPRESSION

All multi-line filters can be supplied with integral transient suppression fitted between each input terminal and earth.

Varistor rating: 275V a.c. 45 Joules (10/1000μs)

To specify the transient suppressed version, suffix V is added to the filter part number (see ordering code).

TYPICAL INSTALLATION DETAILS

The standard cable entry consists of an end conduit entry hole on the filter input (supply) side and a base conduit exit hole on the output (load) side.

Filters can be supplied with other cable entry positions if required upon request.

ORDERING CODE

DS XXXXX /  X / X e.g. DS233778V

Filter Part Number

Add suffix V for transient suppressed filter