Ultra Low Leakage Power Filter Range

A high performance range of 2 Phase or SP&N, 3 Phase and TP&N Power Line filters with ultra low line to earth leakage current supporting system/equipment compliance with overarching requirements of NATO TEMPEST SDIP-27 and SDIP-29 standards. They provide high attenuation from 100kHz to 10GHz suitable for use in TEMPEST and other secure information handling applications.

Insertion Loss Performance

Typical asymmetric insertion loss shown when measured in reference 50Ω system in accordance with CISPR 17 at all loading conditions.

ow Leakage-TEMPEST-Filter-Graphs

Features

  • 2, 3 or 4 line filters with 16A – 125A current ratings
  • Filter construction typically maintains 100dB at high frequencies
  • Stainless steel enclosure
  • External earth studs on the input and output ends
  • Self-healing feedthrough capacitor technology
  • UL94-V0 insulating materials used
Part NumberCurrent
(A)
No. of LinesVoltage (VAC)Freq (Hz)Max Line to Earth Leakage Current*
(mA)
DC Volt Drop @ Full Load
(mV)
Approx Weight
(kg)
115V250V
50Hz60Hz50Hz60Hz
DS5000116225050/60458105008
DS5000232225050/604581045012
DS5000363225050/604581040018
DS50004100225050/604581035025
DS50005125225050/604581033028
Part NumberCurrent
(A)
No. of LinesVoltage (VAC)Freq (Hz)Max Line to Earth Leakage Current*
(mA)
DC Volt Drop @ Full Load
(mV)
Approx Weight
(kg)
115V250V
50Hz60Hz50Hz60Hz
DS5000616344050/60--81050010
DS5000732344050/60--81045015
DS5000863344050/60--81040022
DS50009100344050/60--81035038
DS50010125344050/60--81033042
Part NumberCurrent
(A)
No. of LinesVoltage (VAC)Freq (Hz)Max Line to Earth Leakage Current*
(mA)
DC Volt Drop @ Full Load
(mV)
Approx Weight
(kg)
115V250V
50Hz60Hz50Hz60Hz
DS50011164440/25050/60--81050015
DS50012324440/25050/60--81045022
DS50013634440/25050/60--81040032
DS500141004440/25050/60--81035042
DS500151254440/25050/60--81033046
  • Marine Applications
  • Low leakage land based platforms and equipment
  • Test Voltage

    • 2250VDC each line to case

    Maximum Line to Earth Capacitance

    • 100nF

    Bleeder/Discharge Resistors

    • (L-E) 10MΩ ± 5%, fitted internally
    • (L-L) 1MΩ ± 5%, fitted internally

    Discharge Time to Below 30V

    • <30s

    Mechanical Fixing

    • External fixing tabs (Fixing hardware not provided)

    Full Load Operating Temperature Range

    • -45ºC to +50ºC

    Storage Temperature Range

    • -55°C to +85°C Storage

    Enclosure Material

    • Ferromagnetic stainless steel EN 1.4003

    Enclosure Material Gauge

    • 1.5mm

    Finish

    • Gloss epoxy paint DEF-STAN 80-161

    Colour

    • Light admiralty grey BS 381C 697
    (The base of the filter, fixing feet and areas around the cable entry/exit holes will be paint free for optimum earth connection)
    All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:
    • Mil-F-15733
    • Mil-Std-220C
    • CISPR17:2011/BS EN 55017:2011
    • UL1283
    • LVD 2014/35/EU
    • NATO STANAG 1008 Ed.9 shipboard supplies
    • DEF-STAN 59-411/MIL-STD-461
    • RoHS (2011/65/EU) & LVD (2014/35/EU)
    • UKCA & CE
    DS XXXXX / X e.g. DS50004C

    DS XXXXX / X

    • Filter Part Number
    • Suffix C for standard cable entry
    • For other cable entries, see Installation Details page