Low Leakage Standard Performance Filter Range

Low Leakage Standard Performance EMI filters for electrical connection to SP&N and TP&N mains distribution systems. The filters offer attenuation against electromagnetic noise present on the power lines between the ranges of 100kHz to 18GHz to 100dB. This range of filters has been designed with the safety feature of no Y2 capacitance connected between phase and case/earth. This protects the case rising to high voltage potential if the earth is lost or a capacitor fails. This makes this range of filters more suited for mobile applications or where low earth leakage is desired. These types of filter produce earth leakage currents depending on the voltage potential between earth and neutral.

Insertion Loss Performance

Asymmetric attenuation shown as measured in 50Ω system, at all loading conditions, in accordance with CISPR-17.
Performance curve meets 100dB attenuation from 100kHz to 18GHz.

Rated CurrentPart NumberDC Resistance
(mΩ)
Earth Leakage*
(mA)
Length
(mm)
Width
(mm)
Height
(mm)
Approximate Weight
(kg)
16ADS2623125154251759012
32ADS2355210255502059516
63ADS2355362572520510523
100ADS2355443076020512028
200ADS2591535082047515080
400ADS2591721001250475150110
Rated CurrentPart NumberDC Resistance
(mΩ)
Earth Leakage*
(mA)
Length
(mm)
Width
(mm)
Height
(mm)
Approximate Weight
(kg)
32ADS2355610455904109524
63ADS2355765572541011042
100ADS2355849578041013555
200ADS25916315082057515085
400ADS2591821501250575150120

Rated Voltage

  • 250VAC (SP&N) 50/60Hz
  • 440/250VAC (TP&N) 50/60Hz

Alternative Voltage

  • Also suitable for 208/120VAC and 480/277VAC
  • Alternative surge arrestors may be required.
  • TP&N filters are also suitable for three phase supplies without neutral. In such installations, the neutral terminal should be left unconnected.

Rated Current

  • 6A to 400A (each individual line, see table)

Current Overload

  • 10 x maximum rated current for 1 sec.
  • 1.5 x max rated current for 10 minutes.

Discharge time

  • 30 seconds to below 30V (filter incorporates discharge resistors)
  • If sockets or plugs are used for connection, ensure that no pins or un-insulated parts are accessible by none qualified personnel upon removal.

Temperature Rise

  • 25°C case rise on full load

Temperature Range

  • -45°C to +85°C Storage
  • -45°C to +50°C Working

MTBF

  • >0.8 million hours (calculated using Mil Hdbk 217D)

Surge Suppression (optional)

  • 275VAC at 215J 10kA 8/20μs
  • All filters can be supplied with an integral metal-oxide varistor, fitted between each input terminal and earth. Add a suffix “V” to end of part code.
  • Mobile Screened Rooms & Generator Supplies
  • Screened Rooms needing low earth current leakage
  • Meets TEMPEST requirement for power filters to NATO SDIP 29/1
  • To achieve compliance to MIL STD 461 & DEF STAN 59 411
All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:
  • Mil-F-15733
  • Mil-Std-220C
  • CISPR17:2011/BS EN 55017:2011
  • UL1283
  • LVD 2014/35/EU
  • DEF-STAN 59-411/MIL-STD-461
  • RoHS (2011/65/EU) & LVD (2014/35/EU)
  • UKCA & CE
DS XXXXX / X / X
  • Filter Part Number
  • Suffix C for standard cable entry
  • For other cable entries, see Installation Details page
  • Add suffix V for transient suppressed filter
e.g. DS2550CV

ORDERING CODE

DS XXXXX / X / X

  • Filter Part Number
  • Suffix C for standard cable entry
  • For other cable entries, see Installation Details page
  • Add suffix V for transient suppressed filter

e.g. DS23550CV