MPE
MPE Limited
Hammond Road
Knowsley Industrial Park Liverpool
L33 7UL
Contact
T: +44 (0)151 632 9100
E: sales@mpe.co.uk

High Current (Low Leakage) Standard Performance Range

This range of filters has been developed for use on high current three phase and neutral mains supplies. These filters employ MPE’s proprietary feedthrough filter design incorporating current compensating inductors to provide very low losses and heat dissipation, hence low running costs.

Insertion Loss Performance

Asymmetric attenuation shown as measured in 50Ω system, at all loading conditions, in accordance with CISPR-17.

High-Current-(Low-Leakage)-Standard-Performance

Rated CurrentPart NumberDC Resistance
(mΩ)
Leakage Current*
(mA)
Length
(mm)
Width
(mm)
Height
(mm)
Approximate Weight
(kg)
800ADS23973A0.132502454864285250
800ADS23973C0.132502304864285250
1200ADS26310A0.0725029001000300300
1200ADS26310C0.0725026001000300300
1600ADS26320A0.0425034001000350350
1600ADS26320C0.0425030001000350350
2400ADS26330A0.0325038001000400450
2400ADS26330C0.0325033001000400450

Rated Voltage

  • 440/250VAC (TP&N) 50/60Hz

Alternative Voltage

  • Also suitable for 480/277VAC
  • Alternative surge arrestors may be required.

Rated Current

  • 800A to 2400A (each individual line, see table)

Current Overload

  • 1.25 x max rated current for 15 minutes.

Discharge time

  • 30 seconds to below 30V (filter incorporates discharge resistors)

Temperature Rise

  • 25°C case rise on full load

Temperature Range

  • -45°C to +85°C Storage
  • -45°C to +50°C Working

MTBF

  • >0.6 million hours (calculated using Mil Hdbk 217D)

Surge Suppression (optional)

  • 275VAC at 215J 10kA 8/20μs
  • All filters can be supplied with an integral metal-oxide varistor, fitted between each input terminal and earth. Add a suffix “V” to end of part code.

Typical Applications

  • Screened Rooms requiring low earth current leakage
  • To achieve compliance to MIL STD 461 & DEF STAN 59 411
All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:
  • Mil-F-15733
  • Mil-Std-220C
  • CISPR17:2011/BS EN 55017:2011
  • UL1283
  • LVD 2014/35/EU
  • DEF-STAN 59-411/MIL-STD-461
  • RoHS (2011/65/EU) & LVD (2014/35/EU)
  • UKCA & CE
DS XXXXX / X / X
  • Filter Part Number
  • Suffix C for standard cable entry
  • For other cable entries, see Installation Details page
  • Add suffix V for transient suppressed filter
e.g. DS26320CV

ORDERING CODE

DS XXXXX / X / X

  • Filter Part Number
  • Suffix C for standard cable entry
  • For other cable entries, see Installation Details page
  • Add suffix V for transient suppressed filter

e.g. DS263200CV