Extended Performance EMC Filter Range

Extended Performance EMI filters for electrical connection to SP&N and TP&N mains distribution systems. The filters offer attenuation against electromagnetic noise present on the power lines between the ranges of 10kHz to 40GHz to 100dB. The supply should have a balanced return current and the case needs a solid low impedance connection to potential earth.

Insertion Loss Performance

Asymmetric attenuation shown as measured in 50Ω system, at all loading conditions, in accordance with CISPR-17.
Performance curve meets 100dB attenuation from 10kHz to 40GHz.

Extended-Performance-EMC-Filter-Range

Rated CurrentPart NumberDC Resistance
(mΩ)
Earth Leakage*
(A)
Length
(m)
Width
(mm)
Height
(mm)
Approximate Weight
(kg)
16ADS25942251.85502059516
32ADS25943101.85502059518
63ADS2594481.864020512022
100ADS2594551.866047513560
200ADS260602475050016075
400ADS260620.44.41050525185110
Rated CurentPart NumberDC Resistance (mΩ)Earth Leakage* (A)Length
(mm)
Width
(mm)
Height
(mm)
Approximate Weight
(kg)
16ADS25948252.25504109522
32ADS25949102.25504109524
63ADS2595083.1566041013545
100ADS2595156.366057515070
200ADS2606127.875070017095
250ADS5002416.31200700200120
400ADS260630.49.451700700170200

Rated Voltage

  • 250VAC (SP&N) 50/60Hz
  • 440/250VAC (TP&N) 50/60Hz

Alternative Voltage

  • Also suitable for 208/120VAC and 480/277VAC
  • Alternative surge arrestors may be required.
  • TP&N filters are also suitable for three phase supplies without neutral. In such installations, the neutral terminal should be left unconnected.

Rated Current

  • 6A to 400A (each individual line, see table)

Current Overload

  • 10 x maximum rated current for 1 sec.
  • 1.5 x max rated current for 10 minutes.

Discharge time

  • 30 seconds to below 30V (filter incorporates discharge resistors)
  • If sockets or plugs are used for connection, ensure that no pins or un-insulated parts are accessible by none qualified personnel upon removal.

Temperature Rise

  • 25°C case rise on full load

Temperature Range

  • -45°C to +85°C Storage
  • -45°C to +50°C Working

MTBF

  • >0.8 million hours (calculated using Mil Hdbk 217D)

Surge Suppression (optional)

  • 275VAC at 215J 10kA 8/20μs
  • All filters can be supplied with an integral metal-oxide varistor, fitted between each input terminal and earth. Add a suffix “V” to end of part code.
  • Screened Rooms, Server Supplies & EMC Test Chambers
  • Meets TEMPEST requirement for power filters to NATO SDIP 29/1
  • Supports compliance to MIL STD 461 & DEF STAN 59 411
  • All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards: All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:
    • Mil-F-15733
    • Mil-Std-220C
    • CISPR17:2011/BS EN 55017:2011
    • UL1283
    • LVD 2014/35/EU
    • DEF-STAN 59-411/MIL-STD-461
    • RoHS (2011/65/EU) & LVD (2014/35/EU)
    • UKCA & CE
    DS XXXXX / X / X
    • Filter Part Number
    • Suffix C for standard cable entry
    • For other cable entries, see Installation Details page
    • Add suffix V for transient suppressed filter
    e.g. DS26060CV

    ORDERING CODE

    DS XXXXX / X / X

    • Filter Part Number
    • Suffix C for standard cable entry
    • For other cable entries, see Installation Details page
    • Add suffix V for transient suppressed filter

    e.g. DS26060CV