1500VDC Power Line Filter Range

From screened rooms to industrial power equipment, uncontrolled radio interference presents a common hazard. This range of filters is designed specifically for use on DC supplies up to 1500VDC. These filters have the same robust and reliable construction as MPE’s Power Line AC filter designs providing a long service life and exceptional filtering.

Insertion Loss Performance

Features

  • 2 line applications
  • Utilises MPE self-healing feedthrough capacitors
  • Coupled inductor for high insertion loss
  • UL94-V0 insulating materials used
  • Smaller and lighter than traditional solutions
  • Low heat dissipation
  • Part NumberCurrent Rating
    (A) @ 50°C*
    Performance
    Curve
    Volt Drop Per line @
    Full Load (mV)
    Heat
    Dissipation
    (W)
    Length
    (mm)
    Width
    (mm)
    Height
    (mm)
    Approx
    Weigh
    (kg)
    DS30946161500154251759012
    DS30947321500205502059516
    DS309486313505072520510523
    DS3091710012506076020512028
    DS30918200120012082047515080
    DS3091940011501501250475150110
    DS3092080011002501554500285175
    DS3092112001753501600500300210
    DS3092216001654001800500350350
    DS3092324001605002000500400450
    Part NumberCurrent Rating
    (A) @ 50°C*
    Performance
    Curve
    Volt Drop Per line @
    Full Load (mV)
    Heat
    Dissipation
    (W)
    Length
    (mm)
    Width
    (mm)
    Height
    (mm)
    Approx
    Weigh
    (kg)
    DS309421621200357251759015
    DS3094332212005582035012042
    DS30944632100011597035012062
    DS3091010029002001206350150100
    DS3091120027504001206573162150
    DS3091240022504001750650180240
    DS3091380021503752400500285280
    DS30914120021155502500500300360
    DS30915160021006002900500350440
    DS309162400290750Please consult Sales Department

    Rated Voltage

    • 1500VDC

    Test Voltage

    • 3000VDC each line to case

    Rated Current per Line @ 50°C*

    • See standard and extended performance product tabs

    Insertion Loss

    • Standard Performance: Curve 1 meets 100dB across 100kHz to >10GHz
    • Extended Performance: Curve 2 meets 100dB across 10kHz to >10GHz

    Full Load Maximum Temperature Rise

    • 25°C (16 °C for filters rated >800A)

    Full Load Operating Temperature Rise

    • -45ºC to +50ºC

    No Load Operating Temperature Rise

    • -45ºC to +85ºC

    Maximum Full Load Heat Dissipation

    • See standard and extended performance tabs

    Discharge Resistors

    • Fitted internally from each line to case

    Discharge Time to below 34V

    • < 1 minute

    Maximum Continuous Earth Leakage Current

    • Dependent upon voltage ripple

    Maximum Overload Current Rating

    • 1.25 times rated current for 15 minutes

    Maximum Short Circuit Fault Current Rating

    • 20,000A for 1 second (for filters rated >800A)
  • Secure communications systems
  • Computer installations
  • Portable screened enclosures
  • Electric drive test chambers
  • All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:
    • Mil-F-15733
    • Mil-Std-220C
    • CISPR17:2011/BS EN 55017:2011
    • UL1283
    • LVD 2014/35/EU
    • NATO STANAG 1008 Ed.9 shipboard supplies
    • DEF-STAN 59-411/MIL-STD-461
    • RoHS (2011/65/EU) & LVD (2014/35/EU)
    • UKCA & CE
    DS XXXXX / X / X
    • Filter Part Number
    • Suffix C for standard cable entry
    • For other cable entries, see Installation Details page
    • Add suffix V for transient suppressed filter
    e.g. DS30945CV
    1500VDC Power Line Filters - Issue 5

    DS XXXXX / X / X

    • Filter Part Number
    • Suffix C for standard cable entry
    • For other cable entries, see Installation Details page
    • Add suffix V for transient suppressed filter

    e.g. DS30945CV